| Variable Air Volume (VAV) Box | Modulates the volume of conditioned air supplied to a zone in response to the space temperature or airflow demand. | Air damper, actuator, airflow sensor, controller, and optional heating coil. | Zone temperature control, ventilation-air delivery, airflow balancing, and energy reduction during part-load conditions. | Digital or electronic thermostat signal controlling the damper; reheat may operate when additional heating is required. | Office buildings, schools, hospitals, laboratories, and other multi-zone commercial buildings. |
| Fan Coil Unit | A local fan circulates room air across a water or refrigerant coil to heat or cool the space. | Fan, coil, filter, drain pan, casing, thermostat, and condensate drain when cooling is provided. | Local heating, cooling, air circulation, and limited air filtration. | Room thermostat adjusts fan speed, valve position, or compressor operation. | Hotels, apartments, offices, classrooms, and perimeter zones. |
| Terminal Reheat Unit | Receives centrally cooled air and adds heat locally when a zone requires warming or precise temperature control. | Air damper, airflow sensor, electric heating element or hot-water coil, actuator, and controller. | Fine zone-temperature adjustment, humidity-related airflow management, and minimum ventilation control. | Modulating airflow and heating capacity based on zone temperature and minimum airflow settings. | Buildings requiring close temperature control, including healthcare and laboratory spaces. |
| Induction Unit | High-velocity primary air induces room air through heating or cooling coils, creating secondary airflow without a local fan. | Primary-air nozzle, induction chamber, coil, casing, damper, and control valve. | Zone heating, cooling, air mixing, and perimeter-zone conditioning. | Primary-air volume and water-flow controls respond to room temperature requirements. | Older or specialized commercial buildings, perimeter zones, and spaces needing quiet operation. |
| Chilled Beam | Uses chilled or heated water in a ceiling-mounted coil to exchange heat with the room through convection and, in passive designs, natural air movement. | Water coil, casing, fins, ceiling enclosure, control valve, and separate ventilation-air connection where applicable. | Sensible cooling or heating with low air movement and reduced fan-energy requirements. | Water valve modulation based on room temperature; dew-point control is needed to limit condensation risk. | Modern offices, educational buildings, healthcare areas, and spaces with stable humidity conditions. |
| Radiant Ceiling Panel | Transfers heat between the panel and surrounding surfaces primarily by thermal radiation, with some natural convection. | Metal panel, electric resistance element or hydronic tubing, insulation, suspension system, and controls. | Quiet space heating or cooling without using the panel itself to provide ventilation. | Thermostat controls electrical output or hydronic valve position; ventilation is handled separately. | Offices, classrooms, healthcare spaces, and rooms where low noise is important. |
| Unit Ventilator | Draws in outdoor air and recirculated room air, filters the mixture, and passes it across a heating or cooling coil before supplying it to the room. | Outdoor-air damper, recirculation damper, fan, filter, coil, controls, and sometimes an exhaust-air path. | Ventilation, heating, cooling, air mixing, and zone temperature control. | Thermostat regulates outdoor-air position, fan operation, and heating or cooling output. | Classrooms, perimeter rooms, small offices, and other spaces requiring local outdoor-air ventilation. |
| Displacement Ventilation Terminal | Supplies low-velocity air near the floor; heat from occupants and equipment causes warmer air to rise and leave through high-level exhaust points. | Low-level diffuser or air terminal, plenum, duct connection, airflow-control device, and temperature sensors. | Ventilation, contaminant removal from the occupied zone, and thermal comfort support. | Airflow is controlled according to occupancy, air-quality requirements, or room conditions. | Auditoriums, assembly spaces, industrial areas, and rooms with high ceilings. |
| Air Curtain | Creates a controlled vertical air stream across an open doorway to reduce uncontrolled air exchange between adjacent environments. | Fan, air plenum, discharge nozzle, motor, controls, and optional heating coil. | Reduces infiltration, helps maintain indoor temperature, and can limit the movement of dust or insects. | Door switch, motion sensor, thermostat, or manual control starts the fan and optional heat. | Retail entrances, loading areas, industrial doors, cold rooms, and high-traffic openings. |